Expert Answers for Buyers, Engineers, and Project Teams
Delta Cooling Towers Pvt. Ltd. has prepared this FAQ page to help buyers, consultants, plant engineers, and project teams understand cooling-tower technology, selection, operation, maintenance, materials, efficiency, and costs. Delta has over three decades of industry experience and has supplied more than 30,000 cooling towers.
Cooling Tower Basics
What is a cooling tower and how does it remove heat?
A cooling tower is a specialised heat-rejection system that cools recirculating water by bringing it into direct contact with moving air. When a small portion of water evaporates, it absorbs heat from the remaining water, lowering its temperature before it returns to the process. In simple terms, it converts unwanted process heat into water vapour and releases it into the atmosphere.
How does a cooling tower work?
Hot water from the process enters the cooling tower and is distributed over the fill media through a water-distribution system. A fan mechanically draws ambient air through the tower, causing a small portion of water to evaporate. This evaporation removes heat, and the cooled water collects in the basin before being recirculated to the process.
Why do industries need cooling towers?
Industries need cooling towers to maintain stable operating temperatures for chillers, compressors, furnaces, reactors, heat exchangers, and other heat-generating equipment. Effective cooling protects equipment, supports consistent production quality, reduces energy waste, and helps processes operate reliably under continuous duty.
What are the main components of a cooling tower?
A typical cooling tower includes:
- Casing and basin: House the internal components and collect cooled water.
- Fill media: Increase the contact area between water and air for heat transfer.
- Water-distribution system: Sprays or distributes hot water evenly over the fill.
- Drift eliminators: Reduce water droplets carried out with the exhaust air.
- Fan and motor: Create the required airflow in mechanical-draft towers.
- Louvers and inlet screens: Allow air entry while preventing debris ingress.
- Ladder, access door, and internal supports: Enable inspection, cleaning, and maintenance.
What is the working temperature range of a cooling tower?
A cooling tower works with water in liquid form, so the practical operating range is from 0°C to 100°C. However, for material and performance reasons, Delta generally advises that hot-water inlet temperature should not exceed 60°C.
A cooling tower cannot cool water below the prevailing wet-bulb temperature. In practical selection, a wet-bulb temperature below 20°C is generally not considered, and with a recommended minimum approach of 3°C, the lowest practical cold-water temperature is approximately 23°C. Therefore, a practical cooling range of up to approximately 35°C can be achieved, subject to project-specific conditions and tower selection.
What is the difference between evaporation and heat rejection?
Evaporation is the process by which a small quantity of circulating water changes into vapour. Heat rejection is the total amount of heat removed from the process. In a cooling tower, most of the cooling effect comes from evaporation, while the remaining water becomes cooler and returns to the system.
Types of Cooling Towers
How many types of cooling towers are there?
Cooling towers are commonly classified by airflow direction, draft method, construction, and installation type. The main categories include counter-flow and cross-flow towers, induced-draft and forced-draft towers, packaged and field-erected towers, and open-circuit or closed-circuit systems.
What is an induced-draft cooling tower?
An induced-draft cooling tower uses a fan at the air-discharge point to mechanically pull air through the tower. The fan creates negative pressure inside the tower, drawing ambient air across the fill and improving heat transfer. Delta’s DFC-50, DFC-60, DFC-60 UX, and DPC-70 series use induced-draft principles.
What is a counter-flow cooling tower?
In a counter-flow cooling tower, air moves vertically upward through the tower while hot water flows downward through the fill. This opposite movement improves contact between air and water and supports efficient heat transfer. Delta’s DFC-50, DFC-60, DFC-60 UX, and DPC-70 series are counter-flow cooling towers.
What is the difference between counter-flow and cross-flow cooling towers?
In a counter-flow tower, air travels vertically upward while water flows downward. In a cross-flow tower, air moves horizontally across the falling water. Counter-flow towers are generally more compact, while cross-flow towers can offer lower air-side pressure drop and easier fill access in certain large installations. Delta offers both configurations, including the DPX-80 pultruded FRP cross-flow series.
What is a packaged cooling tower?
A packaged cooling tower is factory-assembled and supplied as a complete unit, making it suitable for projects requiring faster installation and standardised capacity. Smaller-capacity models of Delta’s DFC-50 and DFC-60 series can be supplied in knocked-down (VKD) condition with factory-fitted components for easier transportation and site assembly.
What is a field-erected cooling tower?
A field-erected cooling tower is assembled at the installation site and can be configured for larger capacities, custom layouts, and project-specific requirements. Larger-capacity models of Delta’s DFC-50 and DFC-60 series, as well as all DPC-70 pultruded FRP cooling towers, are field-erected.
Selection and Sizing
How do I select the right cooling tower?
Cooling-tower selection should be based on:
- Required cooling capacity or heat load.
- Water flow rate.
- Hot-water inlet temperature.
- Cold-water outlet temperature.
- Design wet-bulb temperature.
- Available installation space.
- Water quality and treatment approach.
- Noise, drift, and energy requirements.
- Site conditions such as wind load, elevation, and access.
What information is required for a cooling-tower quotation?
For an accurate proposal, share the following details:
- Process or equipment heat load.
- Required water flow rate.
- Hot-water and cold-water temperatures.
- Design wet-bulb temperature.
- Site location and available space.
- Water quality details.
- Country-specific electrical supply characteristics, such as voltage, frequency, and phase.
- Installation constraints, such as rooftop access or restricted height.
- BOQ, technical specification, or layout drawing, if available.
What is cooling range?
Cooling range is the difference between the hot-water temperature entering the tower and the cold-water temperature leaving the tower. It indicates how much heat the tower removes from the circulating water.
What is approach temperature?
Approach is the difference between the cold-water temperature leaving the cooling tower and the design wet-bulb temperature. It is generally advisable to consider an approach of not less than 3°C.
A lower approach requires a larger tower and more heat-transfer surface. It is also important to understand that achieving a lower approach becomes more difficult as the wet-bulb temperature decreases.
What is wet-bulb temperature?
Wet-bulb temperature reflects the lowest temperature to which water can theoretically be cooled by evaporation at a given location. If a cooling tower could cool water exactly to the wet-bulb temperature, it would be operating at 100% efficiency. In practice, this is not possible because a finite temperature difference is required for heat and mass transfer.
Can a cooling tower be installed on a roof?
Yes. Cooling towers can be installed on rooftops where the structure is designed to support the operating weight, water weight, wind loads, vibration, and maintenance access. The tower layout, structural support, and drainage arrangement should be reviewed by a qualified structural engineer.
Can multiple cooling towers be installed together?
Yes. All Delta cooling towers can be installed together to meet higher cooling capacities, provide operational flexibility, or support phased expansion. For towers serving the same application, an equalising line can be provided between the basins to maintain a common water level and support balanced operation.
Can a cooling tower be supplied in multi-cell configuration with a common basin?
Yes. Larger cooling requirements can be met through multi-cell configurations with a common basin, common piping arrangement, and individual fan or cell control. This arrangement supports flexibility, maintenance access, and phased capacity expansion where required.
Performance and Efficiency
How can I improve cooling-tower efficiency?
Cooling-tower efficiency can be improved through:
- Correct tower sizing for the actual heat load.
- Clean and properly distributed water spray.
- Clean, undamaged fill media.
- Correct fan-pitch and motor operation.
- Regular removal of scale, algae, and debris.
- Effective water treatment.
- Proper airflow and prevention of air recirculation.
- Keeping the tower free from airflow restrictions on all sides, including walls, structures, and nearby equipment.
- Timely replacement of worn components.
Why is my cooling tower not achieving the required cold-water temperature?
Common reasons include:
- Fouled or damaged fill.
- Blocked or uneven water distribution.
- Incorrect water flow rate.
- Fan or motor performance issues.
- Excessive air recirculation.
- Higher-than-design wet-bulb temperature.
- Scale, algae, or biological fouling.
- Incorrect tower selection for the actual heat load.
What is cooling-tower drift?
Drift is the loss of small water droplets carried out of the tower with the exhaust air. Drift eliminators are used to capture these droplets and reduce water loss. Delta’s towers use efficient drift eliminators designed to minimise carryover.
What is blowdown or bleed-off?
Blowdown is the controlled removal of a portion of circulating water to limit the concentration of dissolved salts and minerals. It helps control scale formation and maintain acceptable water chemistry.
Does a cooling tower consume a lot of water?
A cooling tower consumes water mainly through evaporation, drift, and blowdown. Evaporation is necessary for cooling, while drift can be minimised through efficient drift eliminators. Blowdown should be managed through proper water treatment and cycle-of-concentration control.
Materials and Construction
Why is FRP used in cooling towers?
FRP, or fibre-reinforced plastic, is widely used because it is lightweight, strong, corrosion-resistant, and suitable for long-term outdoor exposure. It does not rust like metal and is generally easier to handle and install than heavier construction materials.
What is pultruded FRP?
Pultruded FRP is a high-strength composite material produced by pulling continuous fibre reinforcement through a resin bath and heated die. The process creates dense, consistent structural profiles with excellent strength, dimensional stability, corrosion resistance, and durability.
In Delta’s DPC-70 Series, pultruded FRP is used for structural sections, fill supports, and other load-bearing components, while the casing is made from tough corrugated FRP sheets developed through the hand lay-up process.
What is the difference between FRP and pultruded FRP cooling towers?
Standard FRP cooling towers typically use moulded or hand lay-up FRP panels and components, while pultruded FRP towers use high-strength pultruded structural sections. Pultruded FRP is particularly suitable for larger, field-erected towers and demanding industrial environments. Delta’s DPC-70 and DPX-80 series are pultruded FRP cooling towers.
Are FRP cooling towers suitable for coastal or corrosive environments?
Yes. FRP construction is well suited to coastal, humid, chemical, and corrosive environments because it offers strong resistance to rust, corrosion, moisture, saltwater exposure, chemicals, and UV radiation.
What fill materials are used in cooling towers?
Cooling towers commonly use PVC-based fill media, including honeycomb fills, trickle fills, Optigrid fills, and other low-fouling designs. The appropriate fill depends on water quality, fouling risk, pressure drop, and required thermal performance.
Water Quality and Maintenance
What causes scale formation in cooling towers?
Scale forms when dissolved minerals in circulating water become concentrated and deposit on heat-transfer surfaces, fill media, piping, and equipment. Hard water, high cycles of concentration, poor blowdown control, and inadequate water treatment can accelerate scaling.
How can scale and fouling be prevented?
Scale and fouling can be controlled through:
- Proper water treatment.
- Controlled blowdown.
- Regular basin cleaning.
- Fill inspection and cleaning.
- Monitoring of water chemistry.
- Use of suitable filtration or non-chemical treatment devices.
- Prompt removal of algae, debris, and biological growth.
What is the Delta Device?
The Delta Device is a non-chemical water-treatment device designed to help keep minerals suspended in water, reducing their ability to form hard, brittle scale in pipes and equipment. It is intended to support cooling-tower water-management programmes.
How often should a cooling tower be serviced?
Service frequency depends on operating hours, water quality, environmental conditions, and application. As a general practice, inspect the tower regularly, clean the basin and distribution system periodically, check fan and motor condition, inspect fills and drift eliminators, and review water-treatment performance.
What maintenance does a cooling tower require?
Typical maintenance includes:
- Cleaning the cold-water basin.
- Inspecting and cleaning nozzles or distribution system.
- Checking fill condition and airflow.
- Inspecting fan, motor, gearbox, and drive components.
- Checking drift eliminators and louvers.
- Monitoring water chemistry and blowdown.
- Inspecting structural components, fasteners, and seals.
- Replacing worn or damaged spares.
- For gear-driven towers, replacing gearbox oil periodically as recommended by the manufacturer.
Common Industry Problems
What are the most common cooling-tower problems?
The most common issues include scale formation, biological fouling, corrosion, poor water distribution, fill blockage, drift loss, fan or motor failure, excessive noise, water leakage, and insufficient cooling capacity. Many of these problems can be prevented through correct selection, proper installation, and planned maintenance.
Why does a cooling tower produce noise?
Noise may result from fan operation, airflow turbulence, motor or gearbox issues, loose components, water splashing, or improper installation. Correct fan selection, balanced rotating parts, proper alignment, and regular maintenance can help reduce noise.
Why does a cooling tower leak?
Leaks can occur due to damaged casing or basin joints, degraded sealant, cracked FRP panels, improper installation, structural movement, or physical damage. Regular inspection and timely repair help prevent water loss and structural damage.
Why does cooling-tower performance reduce over time?
Performance can reduce due to scale, algae, fouled fill, blocked nozzles, damaged drift eliminators, restricted airflow, fan issues, incorrect water flow, or changes in process heat load. Regular inspection and preventive maintenance help maintain performance.
Delta Cooling Towers
Who is Delta Cooling Towers Pvt. Ltd.?
Delta Cooling Towers Pvt. Ltd. is an Indian cooling-tower manufacturer with more than three decades of experience and over 30,000 cooling-tower installations. The company manufactures FRP cooling towers, CTI-certified cooling towers, pultruded cooling towers, and related products.
What products does Delta offer?
Delta offers:
- DFC-50 Series: Round bottle-shaped FRP cooling towers.
- DFC-60 Series: Square or rectangular modular induced-draft counter-flow cooling towers.
- DFC-60 UX Series: CTI-certified cooling towers.
- DPC-70 Series: Pultruded FRP field-erected induced-draft counter-flow cooling towers.
- DPX-80 Series: Pultruded FRP induced-draft cross-flow cooling towers.
- Delta Device: Non-chemical water-treatment device.
- Cooling-tower spare parts.
Are Delta cooling towers CTI certified?
Yes. Delta’s DFC-60 UX and DFC-60 HUX lines are certified by the Cooling Technology Institute under CTI STD-201 for thermal performance. Delta’s CTI certification has been in effect since 2018.
Where does Delta manufacture its cooling towers?
Delta has manufacturing facilities in three Indian states:
- Delhi: Bawana industrial area, Delhi.
- Uttar Pradesh: Baghpat industrial area, Uttar Pradesh.
- Maharashtra: Works located on the Mumbai–Pune Highway at Khopoli, Maharashtra.
Where does Delta serve?
Delta serves customers across India, including all states and union territories.
States: Andhra Pradesh, Arunachal Pradesh, Assam, Bihar, Chhattisgarh, Goa, Gujarat, Haryana, Himachal Pradesh, Jharkhand, Karnataka, Kerala, Madhya Pradesh, Maharashtra, Manipur, Meghalaya, Mizoram, Nagaland, Odisha, Punjab, Rajasthan, Sikkim, Tamil Nadu, Telangana, Tripura, Uttar Pradesh, Uttarakhand, and West Bengal.
Union Territories: Andaman and Nicobar Islands, Chandigarh, Dadra and Nagar Haveli and Daman and Diu, Delhi, Jammu and Kashmir, Ladakh, Lakshadweep, and Puducherry.
How can I request a quotation from Delta?
You can submit your project details through Delta’s website enquiry form, email your BOQ or technical specification, or contact the sales team. Delta states that it responds to website quotation requests within 24 hours.
Contact:
Delta Cooling Towers Pvt. Ltd.
Corporate Office: 1st Floor, Bhagwati Sadan, Plot No. 8, Community Centre, BH Block (E), Shalimar Bagh, Delhi-110088, India.
Phone: +91-9811156637
Email: delta@deltactowers.com